The utility requires WIMS additional info fields be setup as follows for the Variable (VARDESC) table and the data (DATATBL,DATADDH, etc...) tables.
Variable Additional Info Field Setup:
LIMS_TABLE_NM NVARCHAR2(50) DEFAULT NULL,
LIMS_COLUMN_NM NVARCHAR2(50) DEFAULT NULL,
LIMS_CONVERSION_FACTOR_NUM FLOAT(126) DEFAULT NULL,
LIMS_DECIMAL_PLACES_NUM NUMBER DEFAULT NULL,
LIMS_TS_VARID NUMBER DEFAULT NULL,
LIMS_PT_GROUP NVARCHAR2(50)
To setup the variable Additional Info fields, log into the WIMS client, and go to:


Data Additional Info Field Setup:
SENT_TO_LIMS_DATE (DATE type field): Will be set to the date/time that the data is pushed to the LIMS tables. The Utility checks that the SENT_TO_LIMS_DATE is set to Null before pushing the data. Therefore, this field prevents a data point from getting pushed to LIMS more than once. If you need to push data a second time you MUST clear this field. In a data entry form (such as Monthly Data Entry), bring up the point, right click and choose Additional Info:

To setup the Data Additional Info fields, log into the WIMS client, and go to: