Home : Products : OPS 32 : Interfaces : WWDDE Utility gives Error 282 – Cant perform the DDE operation
Q10022 - ERRMSG: WWDDE Utility gives Error 282 – Cant perform the DDE operation
Problem:

WWDDE Utility gives Error 282 – Cant perform the DDE operation.

Solution:

1.HistData is not running.  Start HistData.exe.

2.No tags crossed referenced to an OPS 32 Variable.  Add some Tag Names to some variables.

3.HistData is running but not connected to the Wonderware database.  This one can happen if HistData is fired in the start up of the computer.  Because HistData starts much faster than Wonderware Intouch, the database is not ready to be connected to by HistData and it does not give an error!  Take HistData out of the computer’s Startup routine.  I think Wonderware can be told to fire the HistData program when it is ok to do so.

Related Articles
No Related Articles Available.

Article Attachments
No Attachments Available.

Related External Links
No Related Links Available.
Help us improve this article...
What did you think of this article?

poor 
1
2
3
4
5
6
7
8
9
10

 excellent
Tell us why you rated the content this way. (optional)
 
Approved Comments...
Jan You rock! Approved: 12/18/2003 7:31 PM
Created on 12/18/2003 4:09 PM.
Last Modified on 4/30/2008 9:30 AM.
Last Modified by No Author Name Available!.
Article has been viewed 5059 times.
Rated 8 out of 10 based on 5 votes.
Print Article
Email Article